Pumping station Aquapump Medium
Duo, GTF 1200, 1800-2250 mm, B
KESSEL Pumping station Aquapump Medium, Duo, wastewater without sewage, load class B 125, installation depth 1800 - 2250 mm, height 103 mm, with 2 submersible GTF 1200 pumps, level measurement pneumatic
- Maximum safety
- LW 600 chamber system suitable for underground installation
- Preconfigured in the factory
Item no. | 826831B |
---|---|
GTIN | 4026092045671 |
Price group | 60 |
Pumping station Aquapump Medium Duo, GTF 1200, 1800-2250 mm, B
The pumping station without sewage wastewater is equipped with one or two submersible pumps and a backflow preventer. The collection tank is an LW 600 chamber system made of permanently resistant polymer (PE-LLD) with open pump tank and universal connection options. Quick-release closures enable the integrated components to be removed easily. Variant Type of system: duo pump Passage seal for conduit pipe (DN): 100 Passage seal for ventilation pipe (DN): 100 Installation: Wet installation Pump control: Control unit Backflow preventer: integrated Pressure pipe connection: horizontal Chamber system: LW 600 General characteristics Colour: black Standard: EN 12050-2 Type of wastewater: without sewage Installation situation: underground installation Delivery state: Modular set for assembly on site System type: Duo ATEX: no Dimensions Net weight: 142 kg Gross weight: 154 kg Groundwater resistant from lower edge of base section: 2000 mm Installation depth: 1800 - 2250 mm Type of height adjustability: vertically adjustable upper section Length: 806 mm Width: 806 mm Packaging dimension: length: 1200 mm Packaging dimension: width: 800 mm Packaging dimension: height: 2220 mm Tank/drain body Pressure pipe connection (DN): 32 Pressure pipe connection (OD): 40 mm Connection conduit pipe (DN): 100 Venting connection (DN): 100 Distance from centre of outlet pipe to tank bottom: 1394 mm Distance pipe bottom inlet to tank bottom: 400 mm Distance from centre of inlet pipe to tank bottom: 455 mm Inlet nominal size (OD): 160 mm Inlet nominal size (DN): 150 mm Number of inlets: 1 Clear width of tank (LW): 600 mm Clear width of entry (LW): 600 mm Coverage features Type of cover: Round cover plate Cover material: Grey iron Colour of cover: black Width of cover: 648 mm Height of cover: 103 mm Length of cover: 648 mm Locking: unlocked Load class: B 125 (EN 124) Pumping device Pump: GTF 1200 Number of pumps: 2 Weight, pump: 10 kg Connection type: coded plug Rated current: 6,2 A Protection class: I Insulation class: F Cos phi - power factor: 0,98 Protection class (pump): IP 68 (3m) Temperature monitoring: integrated Max. temperature (permanent) of conveyed material: 40 °C Max. pumping capacity: 15,5 m³/h Max. pumping height: 9 m Speed: 2650 U/min Power P1: 1,4 kW Power P2: 0,84 kW Operating mode: S1 Type of pump connection cable: H07RN-F 3G 1.5 mm² Impeller type: Multi-vane impeller Length of mains cable for pump: 10 m Control Control unit: Comfort Alarm sensor: optical probe Level measurement instrument: Submersible pressure switch Type of level measurement: pneumatic Protection class control unit: IP 54 Operating voltage: 230 V Connection type: coded plug Length of mains cable for control unit: 1,4 m Potential-free contact: optional GSM interface: yes USB interface: yes Log book function: yes Multi-line display: yes Battery buffering: yes Self-diagnosis system (SDS): yes
Title | Item no. |
---|
Title | Item no. |
---|
Title | Item no. | ||
---|---|---|---|
Basic alarm unit with electronic probe | 20222 | Show | |
Basic alarm unit with optical probe | 20223 | Show | |
Compressor set for air bubbling | 28048 | Show | |
TeleControl GSM modem for Comfort control units 230V/400V | 28792 | Show | |
Connection box for level sensor extension | 28799 | Show | |
Spare part set, optical probe 5 m cable | 80888 | Show | |
Cable accessories Extension for probe | 80889 | Show | |
Cable accessories Extension for pump | 80891 | Show | |
Installation set Thermostat, Hygrostat | 97713 | Show | |
Outdoor Cabinet W: 590 mm,for installation control units | 97714 | Show | |
Warning beacon for outdoor cabinet | 97715 | Show | |
Outdoor Cabinet W: 460 mm, for installation control unit | 97716 | Show | |
Outdoor cabinet W: 785 mm,for installation control units | 97723 | Show | |
Outdoor Cabinet W: 1115mm,for installation control units | 97724 | Show |
Title | Item no. | ||
---|---|---|---|
Splash guard set for optical probe | 28706 | Show | |
Control unit Comfort Duo, 230 V | 28746 | Show | |
One-handed closure for backflow preventer | 680018 | Show | |
Battery 9 V block | 680034 | Show | |
Pressure hose Sold by the metre, 6x4 mm 100 | 680071 | Show | |
Submersible pressure switch without hose | 680108 | Show | |
Clamping ring for upper sections d: 600 mm | 680276 | Show | |
Pump stand for pumping stations | 680362 | Show | |
Spiral housing for passage 30 mm | 680363 | Show | |
Impeller for passage 30 mm | 680366 | Show | |
Riser 1800-2250 mm, from 02/2016 | 680451 | Show | |
Backflow preventer with non-return flap | 680457 | Show | |
Pump connection for pumping stations, from 01/2016 | 680476 | Show | |
Pump connection Duo, suitable for pumping stations | 680480 | Show | |
Seal set 2 non-return flaps, 4 seals | 680491 | Show | |
Replacement pump Aquadive GTF1200 without float switch, 10 m | 680595 | Show | |
One-handed closure for threaded connection | 680698 | Show | |
Sensor clamp for level sensor & subm. press. switch | 680729 | Show | |
Adapter Set optical probe | 80892 | Show | |
Spare part set, optical probe 15 m cable | 80988 | Show | |
Seal for pipe penetration, DN 100 | 850117 | Show | |
Seal for upper sections d: 600 mm | 860116 | Show | |
Cover plate Class B, grey iron with concrete filling | 860131 | Show |
Manuals | |
---|---|
CAD Data | |
Test Reports and Certificates | |
Declaration of Performance | |
Declaration of Conformity |
- CE marking (ce_kennzeichnung): yes
- Type of wastewater (abwasserart_de): without sewage
- Control unit (schaltgeraet): Comfort
- TÜV test mark (pruefzeichen): ID 1111241937
- Installation situation (einbausituation): underground installation
- Load class (belastungsklasse): B 125 (EN 124)
- Pump (pumpe): GTF 1200
- Installation depth (einbautiefe): 1,800 mm
- Impeller type (laufrad_typ): Multi-vane impeller
- Inlet nominal size (DN) (zulauf_nennweite_dn): 150 mm